BESS 55-215kWh Outdoor Cabinet Energy Storage System

Specially designed for small businesses, hospitals, conferences, and areas with weak electrical networks;Integrated with battery cells, PCS, fire protection system, temperature control system, and EMS system, meeting 55-215kWh capacity requirements.

AC Data

Parameter ESSA0030B-0055 ESSA0050B-0055 ESSA0050B-0100 ESSA0100B-0215
Rated Power (kW)305050100
Rated Voltage (V)400
Rated Current (A)437272144
Voltage Range (V)320-460
Rated Frequency (Hz)50/60
Frequency Range (Hz)45-55 / 55-65
THDi (on-grid)<3%
THDu (off-grid)<1% linear; <5% non-linear
Power Factor1 (0.8 lead ~ 0.8 lag adjustable)
Overload Capacity110% continuous
Grid Type3W+N+PE
Isolation Transformer100/400200/400200/400270/400
On/Off-Grid SwitchingSupported

PV Data

Parameter ESSA0030B-0055 ESSA0050B-0055 ESSA0050B-0100 ESSA0100B-0215
Max. PV Input Voltage (V)1,000
Max. PV Power (kW)36/7260/12060/120-
MPPT Operating Voltage Range (V)250-850
Buck-Boost ModeSupported

Battery Data

Parameter ESSA0030B-0055 ESSA0050B-0055 ESSA0050B-0100 ESSA0100B-0215
Cell Type3.2V/120Ah/LFP3.2V/280Ah/LFP
Rated Voltage (V)460.8V, 1P144S460.8V, 1P144S358.4V, 1P112S768V, 1P240S
Rated Energy (kWh)55.29655.296100.352215.04
Operating Voltage Range (V)403.2-511.2403.2-511.2319.2-397.6672-850
Max. Charge/Discharge Rate1C@25℃1C@25℃0.5C@25℃0.5C@25℃
Cycle Life≥3,800 cycles≥3,800 cycles≥6,000 cycles

General Data

Parameter ESSA0030B-0055 ESSA0050B-0055 ESSA0050B-0100 ESSA0100B-0215
Dimensions W×D×H (mm)1,780×1,520×2,2901,780×1,520×2,2901,780×2,2902,460×1,560×2,425
Weight (kg)2,0002,2002,4003,900
Operating Temperature (°C)0 ~ +45
Relative Humidity0 ~ 95% (non-condensing)
Ingress ProtectionIP54
Noise Emission (dB)<75
Max. Operating Altitude (m)5,000 (>3,000 derating)
CoolingIntelligent Air Cooling
Fire Extinguishing SystemAerosols / NOVEC1230 (optional)
DisplayTouch LCD + Cloud Platform
EMS CommunicationRS485, TCP/IP

Key Strengths

Flexible Expansion
Support flexible expansion of PV capacity
📊
Intelligent Prediction
Support battery capacity and discharge time prediction
🔒
Safe & Stable
Integrated EMS function for safe and stable operation
🔌
Strong Load Adaptability
Built-in isolation transformer for strong load adaptability

Applications

Off-Grid Areas
Provide stable power for areas without grid coverage
Power Shortage Areas
Meet electricity needs in power-deficient regions
Remote Rural Areas
Provide reliable power for remote rural communities